PLEASE CHOOSE:

Home | About Us | Which Generator? | Contact us

FAQ- Information to help you choose

 

I have bought a generator, and I am concerned about safety. Can I use a personal power breaker?

Answer : The generator is configured differently to the mains supply. The generator has a ‘floating earth’, whilst the mains has an earthed neutral. Whereas it is definitely recommended to use a personal power breaker (RCD) from the mains, for the majority of cases, it is not necessary to use one with a B&S generator. The generators are safe as they are designed.
Personal power breakers are designed to operate from the mains. If one is to be used with a generator, then it is necessary to modify the generator so that it is configured in the same way as the mains. This is a relatively simple modification for a qualified electrician involving adding a link wire from the neutral terminal to the earth terminal. However, once the generator has been modified, it is necessary to then always use a personal power breaker and to also always use an earth spike, which connects between the generator frame and the ground. Since this is difficult to ensure, it is generally recommended not to modify the generator.


Question : What is the difference between kW and kVA? What is Power factor?

Answer : There are 3 types of electrical:

Real Power, measured in Watts (W). This is the power drawn by a resistive load, e.g. a heater element in a kettle, and has a power factor of 1. (unity power factor, cos F=1, 1.0pf or pf=1)

Reactive Power, measured in Volt Amperes reactive (VAr’s). This is the power drawn by a reactive load (a load with a winding around a core), e.g. an electro-magnet, and has a power factor of 0. (zero power factor, cos F =0, 0pf or pf=0)

Apparent Power, measured in Volt Amperes (VA). Many loads have a combination of resistive and reactive elements. (in fact it is not possible to produce a purely inductive load, since the wire used to form the windings has a resistance). This combination of elements means that both real power (W) and reactive power (VAr) are drawn together.

The proportion of Real Power to Reactive Power is defined as the power factor. [Nearly all resistive load (e.g. Universal motor used in hand tools) then power factor 0.95 to 1.0, nearly all inductive load then power factor ~ 0.3]

The vast majority of single-phase loads have power factors approaching 1. Therefore, single-phase generator power ratings are taken at power factor =1, and are consequently in Watts (W) or kilo Watts (kW), where 1 kW = 1000 W.

Three-phase loads tend to have lower power factors, approaching 0.8, therefore, three phase generator power ratings are taken at power factor =0.8 and are in VA or kVA.

There is obviously a relationship between real power, reactive power, apparent power and power factor….

i) Apparent Power (VA) = Ö [(real power (W))2 + (reactive power (VAr))2]

And

ii) Power factor = Real Power (W)
Apparent Power (VA)

Therefore…

Apparent Power (VA) x Power factor = Real power (W)
If the Power factor =1, then all the Power is real, and
Apparent Power (VA) = Real Power (W)
(W = VA @ 1.0 pf)

For a single-phase generator, the rating should be at 1.0 pf, in which case
Watts = Volt Amperes.
But, for a three-phase generator the rating is at 0.8pf.

This is where confusion can arise!

Example.
A three-phase generator has a continuous rating of 5 kVA at 0.8 pf.

Now, at this rated load, the Real power (kW) will be …

Real Power (kW) = Apparent Power (kVA) x Power factor

Real Power = 5 x 0.8 = 4kW

This means that a generator producing 5kVA at 0.8pf is actually producing 4 kW of Real power, but it is also producing some reactive power.

From i)…
5000 VA = Ö [( 4000 W)2 + ( Reactive Power)2]
Reactive Power = 3000 VAr’s

It is this combination of 4kW of real power and 3kVAr’s of reactive power that has defined the limit for the generator rating.

If the same generator was loaded with a resistive load only, then it may be capable of more than 4kW, however, there is no formula that can be used to find this limit from the 0.8pf rating. It can only be found through testing of each machine.

Similarly, a single-phase generator rated at 4kW, cannot be expected to produce 5kVA at 0.8pf !!!!


Question : Can I operate sensitive equipment from a generator?

Answer : The output from a portable generator is not as stable as the supply from the mains. The speed of the engine driving the alternator is controlled by a simple mechanical governor; consequently, the speed drops as the load is increased. The frequency of the output voltage is directly dependent on the engine speed; therefore, the frequency of the output varies with load. In addition, the output voltage will vary with load, and with temperature. The output voltage of all Generac generators will remain within 230V +/- 10% from no load up to the rated load current quoted on the dataplate. This is the guaranteed range of voltage supplied from the mains utilities.

The frequency of the output voltage will vary typically from 53Hz at no load to 49Hz at rated load current, whereas the mains supply is unlikely to vary by more than 0.1 Hz.
Most electronic equipment is designed to cope with these fluctuations and will operate normally. However, it is always recommended to ask the equipment supplier whether their equipment is suitable to be operated from a portable generator.
As a generator runs out of fuel, the engine is likely to surge. To avoid this affecting electronic equipment an Uninterruptible Power Supply (UPS) can be used. These are typically sold for use with computers so that data is not lost in the event of a power cut.


What size generator do I need to start a motor ?

Answer : This is a tricky one, since there are many different designs of motor, each with different characteristics
Some motors, e.g. Induction type motors (capacitor start/capacitor run) require additional current to start them, therefore requiring a larger generator.
Motors fitted to hand tools generally do not require any additional start-up current.
Consequently, it is recommended to ask the supplier of the equipment that you wish to run whether it requires additional start-up current.
As a rough guide only, allow for a generator that has a continuous rating of 2 ½ to 3 times the motor rating.
Motors can be rated in kW or HP. To convert HP to kW, multiply by ¾.
E.g. What generator to run a 3HP motor?
3HP = 3 x ¾ = 2.25kW.
This motor would require a generator of between;
(2 ½ x 2.25) = 5.625kW
and …
(3 x 2.25) = 6.75kW


Question : I have bought a generator, and would like to connect it to my house in case of mains failure. What do I need to do?

Answer : When using a generator as an alternative supply to the mains, there are several precautions that must be observed.
It is vital that the generator is completely isolated from the mains supply. This ensures that the generator is not attempting to power up the whole neighborhood, but also ensures that it does not electrocute a utility worker trying to restore the mains supply.

To achieve this, a double-pole, break-before-make, changeover switch must be installed by a qualified electrician. Briggs & Stratton manufacture a manual transfer switch for this application. Click Here To View the BTS9200M.
This should be fitted between the electricity meter and the building consumer unit. The switch connects the building to either the mains supply or to a lead which can be plugged into the generator.

Most buildings now have an RCD built into the consumer unit. This is configured to operate from the mains supply with an earthed neutral, and not from a generator with a floating earth. To utilize this protection device, it is necessary to modify the generator so that it is configured in the same way as the mains supply. This is a simple modification for a qualified electrician, involving adding a link wire from the neutral terminal to the earth terminal. It is recommended to make this connection in the plug that is to be used to connect to the generator. This ensures that the generator is unmodified when it is disconnected from the house, and therefore remains safe.

The plug should be labeled “Do not connect to mains: Neutral-Earth link fitted”. The lead between the generator and the transfer switch is not protected by the RCD, it is therefore recommended to use a steel armored cable for this connection.
Finally a local low-impedance earth spike needs to be installed


What size generator do I need for my welder ?

Answer : A welder is rated by its output current. To estimate its input power, divide the output rating by 30.
E.g. A 130A welder will have an input requirement of approximately 130/30=4.3kW. A 200A welder will have an input requirement of approximately 200/30=6.7kW.
This is only an estimate; therefore, it is recommended to choose a generator of the next size up. However, bear in mind, that many users will not actually require the full capacity of their welder, a smaller generator would still operate the welder, but would limit the welding current.



Unsure what Generator power you need?

Then follow the links below:

Power Calculator

FAQ
Need a answer
For More Advice Click Here

Products

Noise information